Read the docs
TI-2019-04846 Aliases CVE-2019-6811GHSA-3xxj-wpwj-gxhm

Improper check for unusual conditions in Schneider Electric Modicon Quantum 140 NOE771x1

Priority LOW 35CWE-754Published · Updated

Key facts

Attack vector
Network
Privileges required
None
User interaction
None
Attack complexity
Low
Impact type
—
Confidentiality · integrity · availability
None · None · High
Fix status
No fix listed

Attack profile from CVSS 3.1 · NVD. Fix status from CNA.

Summary

An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover.

Why it matters now

EPSS 0.0131 70th percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

Not available: CISA has not published SSVC decision points for this record.

Affected products

VendorProductAffected versionsFixed inStatusSource
Schneider ElectricModicon Quantum 140 NOE771x1up to 6.9—No fix listedCNA
  • Modicon Quantum 140 NOE771x1 VendorSchneider Electric Affected up to 6.9 Fixed in — No fix listed CNA

CPE configurations NVD · 4

CPEVersionsRoleVendor
cpe:2.3:o:schneider-electric:modicon_quantum_140noe77101_firmware:*:*:*:*:*:*:*:*up to 6.9VulnerableSchneider Electric
cpe:2.3:h:schneider-electric:modicon_quantum_140noe77101:-:*:*:*:*:*:*:*not specified by NVDRunning onSchneider Electric
cpe:2.3:o:schneider-electric:modicon_quantum_140noe77111_firmware:*:*:*:*:*:*:*:*up to 6.9VulnerableSchneider Electric
cpe:2.3:h:schneider-electric:modicon_quantum_140noe77111:-:*:*:*:*:*:*:*not specified by NVDRunning onSchneider Electric
  • cpe:2.3:o:schneider-electric:modicon_quantum_140noe77101_firmware:*:*:*:*:*:*:*:* Versions up to 6.9 Vulnerable ·Schneider Electric
  • cpe:2.3:h:schneider-electric:modicon_quantum_140noe77101:-:*:*:*:*:*:*:* Versions not specified by NVD Running on ·Schneider Electric
  • cpe:2.3:o:schneider-electric:modicon_quantum_140noe77111_firmware:*:*:*:*:*:*:*:* Versions up to 6.9 Vulnerable ·Schneider Electric
  • cpe:2.3:h:schneider-electric:modicon_quantum_140noe77111:-:*:*:*:*:*:*:* Versions not specified by NVD Running on ·Schneider Electric

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2019-6811
  2. 2026-10-03 Alias added: GHSA-3xxj-wpwj-gxhm

References

  • TI-2022-17384 Integer underflow in Schneider Electric Modicon M340 CPU CVSS 3.1HIGH 7.5
  • TI-2020-06087 Buffer overflow in Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy… CVSS 3.1HIGH 8.8
  • TI-2020-06086 Out-of-bounds write in Web Server on Modicon M340, Modicon Quantum and Modicon Premium… CVSS 3.1HIGH 8.8
  • TI-2020-06085 Out-of-bounds read in Web Server on Modicon M340, Modicon Quantum and Modicon Premium… CVSS 3.1HIGH 8.1

Sources