Read the docs
TI-2021-18281 Aliases CVE-2021-41542GHSA-fmgx-xc2g-vrvv

Cross-site scripting in Siemens Climatix POL909

Priority LOW 28CWE-79Published · Updated

Key facts

Attack vector
Network
Privileges required
None
User interaction
Required
Attack complexity
Low
Impact type
Cross-site scripting
Confidentiality · integrity · availability
Low · Low · None
Fix status
Fixed

Attack profile from CVSS 3.1 · NVD. Fix status from CNA. Impact type from CWE-79.

Summary

A vulnerability has been identified in Climatix POL909 (AWB module) (All versions < V11.44), Climatix POL909 (AWM module) (All versions < V11.36). The User Management page of affected devices is vulnerable to cross-site scripting (XSS). The vulnerability allows an attacker to send malicious JavaScript code which could result in hijacking of the user's cookie/session tokens, redirecting the user to a malicious webpage and performing unintended browser action.

Why it matters now

EPSS 0.00562 46th percentileScored 2026-11-07
Fix Fixed Climatix POL909 (AWB module) (Siemens): V11.44Climatix POL909 (AWM module) (Siemens): V11.36

SSVC decision points

Not available: CISA has not published SSVC decision points for this record.

Affected products

VendorProductAffected versionsFixed inStatusSource
SiemensClimatix POL909 (AWB module)before V11.44V11.44Patch availableCNA
SiemensClimatix POL909 (AWM module)before V11.36V11.36Patch availableCNA
  • Climatix POL909 (AWB module) VendorSiemens Affected before V11.44 Fixed in V11.44 Patch available CNA
  • Climatix POL909 (AWM module) VendorSiemens Affected before V11.36 Fixed in V11.36 Patch available CNA

CPE configurations NVD · 3

CPEVersionsRoleVendor
cpe:2.3:o:siemens:climatix_pol909_firmware:*:*:*:*:advanced_web_module:*:*:*before 11.36VulnerableSiemens
cpe:2.3:o:siemens:climatix_pol909_firmware:*:*:*:*:advanced_web_and_bacnet_module:*:*:*before 11.44VulnerableSiemens
cpe:2.3:h:siemens:climatix_pol909:-:*:*:*:*:*:*:*not specified by NVDRunning onSiemens
  • cpe:2.3:o:siemens:climatix_pol909_firmware:*:*:*:*:advanced_web_module:*:*:* Versions before 11.36 Vulnerable ·Siemens
  • cpe:2.3:o:siemens:climatix_pol909_firmware:*:*:*:*:advanced_web_and_bacnet_module:*:*:* Versions before 11.44 Vulnerable ·Siemens
  • cpe:2.3:h:siemens:climatix_pol909:-:*:*:*:*:*:*:* Versions not specified by NVD Running on ·Siemens

Remediation

  • Fix · CNA Climatix POL909 (AWB module) (Siemens) Fixed in V11.44
  • Fix · CNA Climatix POL909 (AWM module) (Siemens) Fixed in V11.36

Timeline

  1. 2026-10-02 Threatist record created from CVE-2021-41542
  2. 2026-10-03 Alias added: GHSA-fmgx-xc2g-vrvv

References

  • TI-2021-17435 Cleartext transmission of sensitive information in Siemens Climatix POL909 CVSS 3.1HIGH 7.4
  • TI-2021-18282 Improper access control in Siemens Climatix POL909 CVSS 3.1MEDIUM 6.5
  • TI-2021-18280 Cross-site scripting in Siemens Climatix POL909 CVSS 3.1MEDIUM 6.1
  • TI-2020-06098 Cross-site scripting in Siemens Climatix POL908 CVSS 3.1MEDIUM 6.1
  • TI-2020-06097 Cross-site scripting in Siemens Climatix POL908 CVSS 3.1MEDIUM 6.1

Sources