Missing authentication in Delta Electronics InfraSuite Device Master
Key facts
- Attack vector
- Network
- Privileges required
- None
- User interaction
- None
- Attack complexity
- Low
- Impact type
- Security bypass
- Confidentiality · integrity · availability
- High · High · High
- Fix status
- No fix listed
Attack profile from CVSS 3.1 · CNA. Fix status from CNA. Impact type from CWE-306.
Summary
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Why it matters now
SSVC decision points
CISA ADP · SSVC 2.0.3
- Exploitation
- None
- Automatable
- Yes
- Technical impact
- Total
The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.
Affected products
| Vendor | Product | Affected versions | Fixed in | Status | Source |
|---|---|---|---|---|---|
| Delta Electronics | InfraSuite Device Master | up to 00.00.01a | — | No fix listed | CNA |
- InfraSuite Device Master VendorDelta Electronics Affected up to 00.00.01a Fixed in — No fix listed CNA
Remediation
No fixed version listed by the sources yet.
Timeline
- 2026-10-02 Threatist record created from CVE-2022-40202
- 2026-10-03 Alias added: GHSA-qmpg-9h7f-2x2x
References
More Delta Electronics vulnerabilities
- TI-2021-16010 Delta Electronics DOPSoft 2 Out-of-Bounds Write KEVCVSS 3.1HIGH 7.8
- TI-2023-01071 Deserialization of untrusted data in Delta Electronics InfraSuite Device Master CVSS 3.1CRITICAL 9.8
- TI-2024-04235 Delta Electronics DIAEnergie SQL Injection CVSS 3.1HIGH 7.5
- TI-2024-04234 Delta Electronics DIAEnergie SQL Injection CVSS 3.1CRITICAL 9.8
- TI-2022-20149 Path traversal in Delta Electronics InfraSuite Device Master CVSS 3.1CRITICAL 9.8
- TI-2024-18749 Delta Electronics DIAEnergie Path traversal CVSS 3.1HIGH 8.1
Sources
- CVE-2022-40202 · CVE Program
- CVE-2022-40202 · NVD
- FIRST EPSS
- GHSA-qmpg-9h7f-2x2x · GitHub Advisory Database · CC BY 4.0
This product uses the NVD API but is not endorsed or certified by the NVD. Sources and licences