Rockwell Automation FactoryTalk System Services Vulnerable to Sensitive Information Disclosure
Key facts
- Attack vector
- Network
- Privileges required
- None
- User interaction
- Required
- Attack complexity
- Low
- Impact type
- Security bypass
- Confidentiality · integrity · availability
- Low · None · None
- Fix status
- No fix listed
Attack profile from CVSS 3.1 · NVD. Fix status from CNA. Impact type from CWE-346.
Summary
The underlying feedback mechanism of Rockwell Automation's FactoryTalk System Services that transfers the FactoryTalk Policy Manager rules to relevant devices on the network does not verify that the origin of the communication is from a legitimate local client device. This may allow a threat actor to craft a malicious website that, when visited, will send a malicious script that can connect to the local WebSocket endpoint and wait for events as if it was a valid client device. If successfully exploited, this would allow a threat actor to receive information including whether FactoryTalk Policy Manager is installed and potentially the entire security policy.
Why it matters now
SSVC decision points
CISA ADP · SSVC 2.0.3
- Exploitation
- None
- Automatable
- No
- Technical impact
- Total
The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.
Affected products
| Vendor | Product | Affected versions | Fixed in | Status | Source |
|---|---|---|---|---|---|
| Rockwell | FactoryTalk System Services | up to 6.20 | — | No fix listed | CNA |
- FactoryTalk System Services VendorRockwell Affected up to 6.20 Fixed in — No fix listed CNA
Remediation
No fixed version listed by the sources yet.
Timeline
- 2026-10-02 Threatist record created from CVE-2023-2639
- 2026-10-03 Alias added: GHSA-vhfm-8gx7-f4cp
References
More Rockwell Factorytalk Policy Manager vulnerabilities
- TI-2023-02466 Rockwell Automation FactoryTalk System Services Vulnerable To Use Of Hard-Coded Cryptographic Key CVSS 3.1HIGH 8.2
- TI-2024-05869 Rockwell Automation Unsecured Private Keys in FactoryTalk® System Services CVSS 4.0MEDIUM 6.0
- TI-2023-02467 Rockwell Automation FactoryTalk System Services Vulnerable to a Denial-of-Service Attack CVSS 3.1MEDIUM 5.9
- TI-2024-05870 Rockwell Automation Unsecured Private Keys in FactoryTalk® System Services CVSS 4.0LOW 1.8
Sources
- CVE-2023-2639 · CVE Program
- CVE-2023-2639 · NVD
- FIRST EPSS
- GHSA-vhfm-8gx7-f4cp · GitHub Advisory Database · CC BY 4.0
This product uses the NVD API but is not endorsed or certified by the NVD. Sources and licences