Read the docs
TI-2025-03308 Aliases CVE-2025-3756GHSA-h84p-pw6f-c6p6

Denial of Service Vulnerabilities in System 800xA, Symphony® Plus IEC 61850

Priority LOW 30CWE-1284Published · Updated

Key facts

Attack vector
Adjacent network
Privileges required
None
User interaction
None
Attack complexity
Low
Attack requirements
None
Impact type
—
Confidentiality · integrity · availability
None · None · High
Fix status
No fix listed

Attack profile from CVSS 4.0 · CNA. Fix status from CNA.

Summary

A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.  The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.     This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

Why it matters now

Exploitation None reported CISA SSVC · not in CISA KEV
EPSS 0.00184 8th percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

CISA ADP · SSVC 2.0.3

Exploitation
None
Automatable
No
Technical impact
Partial

The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.

Affected products

VendorProductAffected versionsFixed inStatusSource
ABBAC800M (System 800xA)6.0.0x – 6.0.0303.0; 6.1.0x – 6.1.0031.0; 6.1.1x – 6.1.1004.0; 6.1.1x – 6.1.1202.0; 6.2.0x – 6.2.0006.0—No fix listedCNA
ABBSymphony Plus SD SeriesA_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005—No fix listedCNA
ABBSymphony Plus MR (Melody Rack)3.10 – 3.52—No fix listedCNA
ABBS+ Operations2.1; 2.2; 2.3; 3.3—No fix listedCNA
  • AC800M (System 800xA) VendorABB Affected 6.0.0x – 6.0.0303.0; 6.1.0x – 6.1.0031.0; 6.1.1x – 6.1.1004.0; 6.1.1x – 6.1.1202.0; 6.2.0x – 6.2.0006.0 Fixed in — No fix listed CNA
  • Symphony Plus SD Series VendorABB Affected A_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005 Fixed in — No fix listed CNA
  • Symphony Plus MR (Melody Rack) VendorABB Affected 3.10 – 3.52 Fixed in — No fix listed CNA
  • S+ Operations VendorABB Affected 2.1; 2.2; 2.3; 3.3 Fixed in — No fix listed CNA

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2025-3756
  2. 2026-10-03 Alias added: GHSA-h84p-pw6f-c6p6

References

  • TI-2019-03985 ABB MicroSCADA Pro SYS600 Missing Authentication for Critical Function CVSS 3.1CRITICAL 9.8
  • TI-2019-05127 The ABB IDAL HTTP server is vulnerable to a buffer overflow when a long Host header is… CVSS 3.1HIGH 8.8
  • TI-2024-05845 Remote code execution in ABB ASPECT-Enterprise CVSS 4.0CRITICAL 9.4
  • TI-2024-34459 Service control in ABB ASPECT-Enterprise CVSS 4.0HIGH 8.8
  • TI-2024-05758 unauthorized file access CVSS 4.0CRITICAL 9.4
  • TI-2022-00806 ABB Flow Computer and Remote Controllers Path Traversal Vulnerability in Totalflow TCP protocol can lead to root access CVSS 3.1CRITICAL 9.8
See all 262 →

Sources