Read the docs
TI-2025-03491 Aliases CVE-2025-3947GHSA-96x3-56x6-r6f5

Integer underflow during processing of short network packets in CDA FTEB responder

Priority LOW 36CWE-191Published · Updated

Key facts

Attack vector
Network
Privileges required
None
User interaction
None
Attack complexity
Low
Impact type
—
Confidentiality · integrity · availability
None · Low · High
Fix status
No fix listed

Attack profile from CVSS 3.1 · CNA. Fix status from CNA.

Summary

The Honeywell Experion PKS contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in improper integer data value checking during subtraction leading to a denial of service. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.

Why it matters now

Exploitation None reported CISA SSVC · not in CISA KEV
EPSS 0.00367 30th percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

CISA ADP · SSVC 2.0.3

Exploitation
None
Automatable
No
Technical impact
Partial

The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.

Affected products

VendorProductAffected versionsFixed inStatusSource
HoneywellC300 PCNT02520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellC300 PCNT05520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellFIM4520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellFIM8520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellUOC520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellCN100520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellHCA520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellC300PM520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
HoneywellC200E520.1 – 520.2 TCU9; 530 – 530 TCU3—No fix listedCNA
  • C300 PCNT02 VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • C300 PCNT05 VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • FIM4 VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • FIM8 VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • UOC VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • CN100 VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • HCA VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • C300PM VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA
  • C200E VendorHoneywell Affected 520.1 – 520.2 TCU9; 530 – 530 TCU3 Fixed in — No fix listed CNA

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2025-3947
  2. 2026-10-03 Alias added: GHSA-96x3-56x6-r6f5

References

  • TI-2023-03466 Printer web page invalid command execution CVSS 3.1CRITICAL 9.9
  • TI-2021-22482 WIN-PACK PRO 4.8 - 'WPCommandFileService' Unquoted Service Path CVSS 4.0HIGH 8.5
  • TI-2021-22480 WIN-PACK PRO 4.8 - 'GuardTourService' Unquoted Service Path CVSS 4.0HIGH 8.5
  • TI-2007-02844 Buffer overflow in the BaseRunner ActiveX control in the Ademco ATNBaseLoader100 Module… CVSS 2.0HIGH 10.0
  • TI-2023-18324 MAS (a Carrier brand) MASmobile Classic Authorization Bypass CVSS 3.1MEDIUM 6.5
  • TI-2023-28253 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
See all 132 →