Read the docs
TI-2025-07734 Aliases CVE-2025-8448GHSA-w6r8-h9q4-qq7v

Information disclosure in Schneider Eelctric EcoStruxure Building Operation Enterprise…

Priority LOW 6CWE-200Published · Updated

Key facts

Attack vector
Adjacent network
Privileges required
Low
User interaction
Passive
Attack complexity
High
Attack requirements
None
Impact type
Information disclosure
Confidentiality · integrity · availability
Low · None · None
Fix status
Fixed

Attack profile from CVSS 4.0 · CNA. Fix status from CNA. Impact type from CWE-200.

Summary

CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause unauthorized access to sensitive credential data when an attacker is able to capture local SMB traffic between a valid user within the BMS network and the vulnerable products.

Why it matters now

Exploitation None reported CISA SSVC · not in CISA KEV
EPSS 0.00198 9th percentileScored 2026-11-07
Fix Fixed EcoStruxure Building Operation Enterprise Server (Schneider Eelctric): 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)EcoStruxure Enterprise Server (Schneider Electric): 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)+1 more product

SSVC decision points

CISA ADP · SSVC 2.0.3

Exploitation
None
Automatable
No
Technical impact
Partial

The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.

Affected products

VendorProductAffected versionsFixed inStatusSource
Schneider EelctricEcoStruxure Building Operation Enterprise ServerAll 7.x versions to before 7.0.2.348; All 6.x versions to before 6.0.4.10001 (CP8); All 5.x versions to before 5.0.3.17009 (CP16)7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)Patch availableCNA
Schneider ElectricEcoStruxure Enterprise ServerAll 7.x versions to before 7.0.2.348; All 6.x versions to before 6.0.4.10001 (CP8); All 5.x versions to before 5.0.3.17009 (CP16)7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)Patch availableCNA
Schneider EelctricEcoStruxure Building Operation WorkstationAll 7.x versions to before 7.0.2.348; All 6.x versions to before 6.0.4.10001 (CP8); All 5.x versions to before 5.0.3.17009 (CP16)7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)Patch availableCNA
  • EcoStruxure Building Operation Enterprise Server VendorSchneider Eelctric Affected All 7.x versions to before 7.0.2.348; All 6.x versions to before 6.0.4.10001 (CP8); All 5.x versions to before 5.0.3.17009 (CP16) Fixed in 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16) Patch available CNA
  • EcoStruxure Enterprise Server VendorSchneider Electric Affected All 7.x versions to before 7.0.2.348; All 6.x versions to before 6.0.4.10001 (CP8); All 5.x versions to before 5.0.3.17009 (CP16) Fixed in 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16) Patch available CNA
  • EcoStruxure Building Operation Workstation VendorSchneider Eelctric Affected All 7.x versions to before 7.0.2.348; All 6.x versions to before 6.0.4.10001 (CP8); All 5.x versions to before 5.0.3.17009 (CP16) Fixed in 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16) Patch available CNA

Remediation

  • Fix · CNA EcoStruxure Building Operation Enterprise Server (Schneider Eelctric) Fixed in 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)
  • Fix · CNA EcoStruxure Enterprise Server (Schneider Electric) Fixed in 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)
  • Fix · CNA EcoStruxure Building Operation Workstation (Schneider Eelctric) Fixed in 7.0.2.348, 6.0.4.10001 (CP8), 5.0.3.17009 (CP16)

Fixed in the same release

Records fixed by the same vendor advisory or release, as the CNA lists them.

  • Release ·

    Schneider Electric EcoStruxure Enterprise Server 5.0.3.17009 (CP16), 6.0.4.10001 (CP8), 7.0.2.348

    2 records Highest priority Priority LOW 2 LOW

    Other records, highest priority first

    • TI-2025-07735 Uncontrolled resource consumption in Schnieder Electric EcoStruxure Building Operation…Priority LOW 19
  • Release ·

    Schneider Eelctric EcoStruxure Building Operation Workstation 5.0.3.17009 (CP16), 6.0.4.10001 (CP8), 7.0.2.348

    2 records Highest priority Priority LOW 2 LOW

    Other records, highest priority first

    • TI-2025-07735 Uncontrolled resource consumption in Schnieder Electric EcoStruxure Building Operation…Priority LOW 19

Timeline

  1. 2026-10-02 Threatist record created from CVE-2025-8448
  2. 2026-10-03 Alias added: GHSA-w6r8-h9q4-qq7v

References

  • TI-2025-07735 Uncontrolled resource consumption in Schnieder Electric EcoStruxure Building Operation… CVSS 4.0MEDIUM 4.1

Sources