Read the docs
TI-2021-14264 Aliases CVE-2021-35533GHSA-wv2v-prmm-j684

Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series

Priority LOW 35CWE-20Published · Updated

Key facts

Attack vector
Network
Privileges required
None
User interaction
None
Attack complexity
Low
Impact type
—
Confidentiality · integrity · availability
None · None · High
Fix status
No fix listed

Attack profile from CVSS 3.1 · CNA. Fix status from CNA.

Summary

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Why it matters now

EPSS 0.0095 61st percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

Not available: CISA has not published SSVC decision points for this record.

Affected products

VendorProductAffected versionsFixed inStatusSource
Hitachi EnergyRTU500 seriesCMU Firmware version 12.0 and later; CMU Firmware version 12.2 and later; CMU Firmware version 12.4 and later—No fix listedCNA
  • RTU500 series VendorHitachi Energy Affected CMU Firmware version 12.0 and later; CMU Firmware version 12.2 and later; CMU Firmware version 12.4 and later Fixed in — No fix listed CNA

CPE configurations NVD · 4

CPEVersionsRoleVendor
cpe:2.3:o:hitachienergy:rtu500_firmware:12.0:*:*:*:*:*:*:*12.0VulnerableHitachi Energy
cpe:2.3:o:hitachienergy:rtu500_firmware:12.2:*:*:*:*:*:*:*12.2VulnerableHitachi Energy
cpe:2.3:o:hitachienergy:rtu500_firmware:12.4:*:*:*:*:*:*:*12.4VulnerableHitachi Energy
cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*not specified by NVDRunning onHitachi Energy
  • cpe:2.3:o:hitachienergy:rtu500_firmware:12.0:*:*:*:*:*:*:* Versions 12.0 Vulnerable ·Hitachi Energy
  • cpe:2.3:o:hitachienergy:rtu500_firmware:12.2:*:*:*:*:*:*:* Versions 12.2 Vulnerable ·Hitachi Energy
  • cpe:2.3:o:hitachienergy:rtu500_firmware:12.4:*:*:*:*:*:*:* Versions 12.4 Vulnerable ·Hitachi Energy
  • cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:* Versions not specified by NVD Running on ·Hitachi Energy

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2021-35533
  2. 2026-10-03 Alias added: GHSA-wv2v-prmm-j684

References

  • TI-2022-03099 IEC 61850 MMS-Server Vulnerability in multiple Hitachi Energy Products CVSS 3.1HIGH 7.5
  • TI-2022-04211 Out-of-bounds write in Hitachi Energy RTU500 series CVSS 3.1HIGH 7.5
  • TI-2022-02312 Improper input validation in Hitachi Energy RTU500 series CVSS 3.1HIGH 7.5
  • TI-2021-08743 Specially Crafted IEC 61850 Protocol Sequence Vulnerability CVSS 3.1HIGH 7.5
  • TI-2022-11258 Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series CVSS 3.1HIGH 7.5
  • TI-2023-06138 Buffer overflow in Hitachi Energy RTU500 series CMU Firmware CVSS 3.1HIGH 7.5

Sources