A vulnerability exists in the ICCP stack of the affected SYS600 versions due to…
Key facts
- Attack vector
- Network
- Privileges required
- None
- User interaction
- None
- Attack complexity
- Low
- Impact type
- —
- Confidentiality · integrity · availability
- None · None · High
- Fix status
- No fix listed
Attack profile from CVSS 3.1 · CNA. Fix status from CNA.
Summary
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Why it matters now
SSVC decision points
CISA ADP · SSVC 2.0.3
- Exploitation
- None
- Automatable
- Yes
- Technical impact
- Partial
The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.
Affected products
| Vendor | Product | Affected versions | Fixed in | Status | Source |
|---|---|---|---|---|---|
| Hitachi Energy | MicroSCADA X SYS600 | 10.2; 10.2.1; 10.3; 10.3.1 | — | No fix listed | CNA |
- MicroSCADA X SYS600 VendorHitachi Energy Affected 10.2; 10.2.1; 10.3; 10.3.1 Fixed in — No fix listed CNA
CPE configurations NVD · 2
| CPE | Versions | Role | Vendor |
|---|---|---|---|
| cpe:2.3:a:hitachienergy:microscada_x_sys600:*:*:*:*:*:*:*:* | 10.2 – 10.3.1 | Vulnerable | Hitachi Energy |
| cpe:2.3:h:hitachienergy:sys600:-:*:*:*:*:*:*:* | not specified by NVD | Running on | Hitachi Energy |
- cpe:2.3:a:hitachienergy:microscada_x_sys600:*:*:*:*:*:*:*:* Versions 10.2 – 10.3.1 Vulnerable ·Hitachi Energy
- cpe:2.3:h:hitachienergy:sys600:-:*:*:*:*:*:*:* Versions not specified by NVD Running on ·Hitachi Energy
Remediation
No fixed version listed by the sources yet.
Timeline
- 2026-10-02 Threatist record created from CVE-2022-2277
- 2026-10-03 Alias added: GHSA-m8wx-w8wv-8q47
References
More Hitachi Energy Microscada X Sys600 vulnerabilities
- TI-2024-07362 The product exposes a service that is intended for local only to all network interfaces without any authentication. CVSS 3.1CRITICAL 9.8
- TI-2024-03713 Path traversal in Hitachi Energy MicroSCADA X SYS600 CVSS 3.1CRITICAL 9.9
- TI-2024-04530 A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. CVSS 3.1CRITICAL 9.9
- TI-2022-12271 Improper input validation in Hitachi Energy MicroSCADA X SYS600 CVSS 3.1HIGH 7.5
- TI-2022-11954 Improper input validation in Hitachi Energy MicroSCADA X SYS600 CVSS 3.1HIGH 7.5
- TI-2022-11952 Improper authorization in Hitachi Energy MicroSCADA X SYS600 CVSS 3.1HIGH 8.8
Sources
- CVE-2022-2277 · CVE Program
- CVE-2022-2277 · NVD
- FIRST EPSS
- GHSA-m8wx-w8wv-8q47 · GitHub Advisory Database · CC BY 4.0
This product uses the NVD API but is not endorsed or certified by the NVD. Sources and licences