Read the docs
TI-2022-12554 Aliases CVE-2022-30319GHSA-vqj4-mpgw-jrqv

Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass.

Priority LOW 38CWE-290Published · Updated

Key facts

Attack vector
Adjacent network
Privileges required
None
User interaction
None
Attack complexity
Low
Impact type
Security bypass
Confidentiality · integrity · availability
High · High · None
Fix status
No fix listed

Attack profile from CVSS 3.1 · NVD. Fix status from CNA. Impact type from CWE-290.

Summary

Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

Why it matters now

Exploitation None reported CISA SSVC · not in CISA KEV
EPSS 0.00704 53rd percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

CISA ADP · SSVC 2.0.3

Exploitation
None
Automatable
No
Technical impact
Total

The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.

Affected products

VendorProductAffected versionsFixed inStatusSource
——all versions—No fix listedCNA
  • — Vendor— Affected all versions Fixed in — No fix listed CNA

CPE configurations NVD · 1

CPEVersionsRoleVendor
cpe:2.3:a:honeywell:saia_pg5_controls_suite:-:*:*:*:*:*:*:*not specified by NVDVulnerableHoneywell
  • cpe:2.3:a:honeywell:saia_pg5_controls_suite:-:*:*:*:*:*:*:* Versions not specified by NVD Vulnerable ·Honeywell

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2022-30319
  2. 2026-10-03 Alias added: GHSA-vqj4-mpgw-jrqv

References

  • TI-2023-28253 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
  • TI-2023-28255 Path traversal in Honeywell Saia PG5 Controls Suite CVSS 3.1HIGH 8.8
  • TI-2023-28251 Path traversal in Honeywell Saia PG5 Controls Suite CVSS 3.1HIGH 8.8
  • TI-2023-28257 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
  • TI-2023-28256 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
  • TI-2023-28254 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
See all 8 →

Sources