Read the docs
TI-2023-01947 Aliases CVE-2023-2071GHSA-5cg3-92mh-qgvc

FactoryTalk View Machine Edition Vulnerable to Remote Code Execution

Priority MEDIUM 59CWE-20Published · Updated

Key facts

Attack vector
Network
Privileges required
None
User interaction
None
Attack complexity
Low
Impact type
Code execution
Confidentiality · integrity · availability
High · High · High
Fix status
No fix listed

Attack profile from CVSS 3.1 · CNA. Fix status from CNA. Impact type from CWE-434.

Summary

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

Why it matters now

Exploitation None reported CISA SSVC · not in CISA KEV
EPSS 0.17274 97th percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

CISA ADP · SSVC 2.0.3

Exploitation
None
Automatable
No
Technical impact
Partial

The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.

Affected products

VendorProductAffected versionsFixed inStatusSource
RockwellFaup to 13.0—No fix listedCNA
  • Fa VendorRockwell Affected up to 13.0 Fixed in — No fix listed CNA

CPE configurations NVD · 2

CPEVersionsRoleVendor
cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:machine:*:*:*up to 13.0VulnerableRockwell
cpe:2.3:h:rockwellautomation:panelview_plus:-:*:*:*:*:*:*:*not specified by NVDRunning onRockwell
  • cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:machine:*:*:* Versions up to 13.0 Vulnerable ·Rockwell
  • cpe:2.3:h:rockwellautomation:panelview_plus:-:*:*:*:*:*:*:* Versions not specified by NVD Running on ·Rockwell

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2023-2071
  2. 2026-10-03 Alias added: GHSA-5cg3-92mh-qgvc

References

  • TI-2020-09688 Improper input validation in Rockwell FactoryTalk View SE CVSS 3.1CRITICAL 9.0
  • TI-2020-09687 Access control flaw in Rockwell FactoryTalk View SE CVSS 3.1HIGH 8.1
  • TI-2020-09686 Information disclosure in Rockwell FactoryTalk View SE CVSS 3.1MEDIUM 4.3
  • TI-2024-04291 Rockwell Automation Datalog Function within in FactoryTalk® View SE contains SQL Injection Vulnerability CVSS 4.0HIGH 8.8
  • TI-2024-30786 FactoryTalk® View Site Edition Remote Code Execution Vulnerability via Lack of Input Validation CVSS 4.0CRITICAL 9.2
  • TI-2024-24878 Rockwell Automation FactoryTalk® View SE v11 Information Leakage Vulnerability via Authentication Restriction CVSS 4.0HIGH 8.2
See all 17 →