Read the docs
TI-2025-00686 Aliases CVE-2025-0814GHSA-mf38-7xr2-g2q7

Improper input validation in Schneider Electric Enerlin’X IFE interface

Priority LOW 37CWE-20Published · Updated

Key facts

Attack vector
Network
Privileges required
None
User interaction
None
Attack complexity
Low
Attack requirements
None
Impact type
—
Confidentiality · integrity · availability
None · None · Low
Fix status
No fix listed

Attack profile from CVSS 4.0 · CNA. Fix status from CNA.

Summary

CWE-20: Improper Input Validation vulnerability exists that could cause Denial-of-Service of the network services running on the product when malicious IEC61850-MMS packets are sent to the device. The core functionality of the breaker remains intact during the attack.

Why it matters now

Exploitation None reported CISA SSVC · not in CISA KEV
EPSS 0.00383 32nd percentileScored 2026-11-07
Fix No fix listed No fixed version in the sources yet

SSVC decision points

CISA ADP · SSVC 2.0.3

Exploitation
None
Automatable
Yes
Technical impact
Partial

The decision (Track, Attend, Act) also depends on your mission and well-being impact; see CISA's SSVC guide.

Affected products

VendorProductAffected versionsFixed inStatusSource
Schneider ElectricEnerlin’X IFE interface (LV434001)All versions—No fix listedCNA
Schneider ElectricEnerlin’X eIFE (LV851001)All versions—No fix listedCNA
  • Enerlin’X IFE interface (LV434001) VendorSchneider Electric Affected All versions Fixed in — No fix listed CNA
  • Enerlin’X eIFE (LV851001) VendorSchneider Electric Affected All versions Fixed in — No fix listed CNA

Remediation

No fixed version listed by the sources yet.

Timeline

  1. 2026-10-02 Threatist record created from CVE-2025-0814
  2. 2026-10-03 Alias added: GHSA-mf38-7xr2-g2q7

References

  • TI-2018-05679 SQL injection in U.motion Builder software version 1.3.4 KEVCVSS 3.1CRITICAL 9.8
  • TI-2021-05589 Hard-coded credentials in EVlink City , EVlink Parking , and EVlink Smart Wallbox CVSS 3.1CRITICAL 9.8
  • TI-2022-15561 OS command injection in Schneider Electric SpaceLogic C-Bus Home Controller CVSS 3.1HIGH 8.8
  • TI-2023-04970 Path traversal in Schneider Electric C-Bus Toolkit CVSS 3.1CRITICAL 9.8
  • TI-2019-04862 Improper handling of exceptional conditions in Schneider Electric Modicon M580 CVSS 3.1HIGH 7.5
  • TI-2018-05690 Improper handling of exceptional conditions in Modicon M580 Modicon M340 Modicon Quantum… CVSS 3.1HIGH 7.5
See all 888 →

Sources