Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic…
Key facts
- Attack vector
- Adjacent network
- Privileges required
- None
- User interaction
- None
- Attack complexity
- Low
- Impact type
- Information disclosure
- Confidentiality · integrity · availability
- Low · None · None
- Fix status
- No fix listed
Attack profile from CVSS 3.1 · NVD. Fix status from CNA. Impact type from CWE-327.
Summary
Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Why it matters now
SSVC decision points
Not available: CISA has not published SSVC decision points for this record.
Affected products
| Vendor | Product | Affected versions | Fixed in | Status | Source |
|---|---|---|---|---|---|
| — | — | all versions | — | No fix listed | CNA |
- — Vendor— Affected all versions Fixed in — No fix listed CNA
Remediation
No fixed version listed by the sources yet.
Timeline
- 2026-10-02 Threatist record created from CVE-2022-30320
- 2026-10-03 Alias added: GHSA-99h8-7hr4-j9f9
References
More Honeywell Saia Pg5 Controls Suite vulnerabilities
- TI-2023-28253 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
- TI-2023-28255 Path traversal in Honeywell Saia PG5 Controls Suite CVSS 3.1HIGH 8.8
- TI-2023-28251 Path traversal in Honeywell Saia PG5 Controls Suite CVSS 3.1HIGH 8.8
- TI-2022-12554 Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. CVSS 3.1HIGH 8.1
- TI-2023-28257 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
- TI-2023-28256 XML external entity injection in Honeywell Saia PG5 Controls Suite CVSS 3.1MEDIUM 6.5
Sources
- CVE-2022-30320 · CVE Program
- CVE-2022-30320 · NVD
- FIRST EPSS
- GHSA-99h8-7hr4-j9f9 · GitHub Advisory Database · CC BY 4.0
This product uses the NVD API but is not endorsed or certified by the NVD. Sources and licences